HB 3314

AN ACT relating to certain energy efficiency performance standards for

House Bill
Filed

Filed

Bill introduced by legislator

Committee

Hearing

Passed Cmte

Calendar

Passed

Sent

Enrolled

Governor

Signed

89th Regular Session

Jan 14, 2025 - Jun 2, 2025 • Session ended

Awaiting Committee Assignment

Bill filed, pending referral to House committee

← Back to Bills

Committee

Not yet assigned

Fiscal Note

Not available

What This Bill Does

Establishes new residential building energy efficiency standards for attic and rafter insulation in Texas. It allows local jurisdictions to consider an unvented attic or rafter assembly compliant with energy codes if it meets specific insulation requirements, including using air impermeable insulation to an R-value of 20 or 26 depending on location, passing a blower door test, and having appropriate mechanical ventilation. The standards aim to improve home energy efficiency and provide consistent guidelines for residential construction across Texas, taking effect on September 1, 2025.

Subject Areas

Bill Text

relating to certain energy efficiency performance standards for
BE IT ENACTED BY THE LEGISLATURE OF THE STATE OF TEXAS:
SECTION 1.  Chapter 388, Health and Safety Code, is amended
by adding Section 388.0045 to read as follows:
Sec. 388.0045.  RESIDENTIAL BUILDING ENERGY EFFICIENCY
PERFORMANCE STANDARDS FOR ATTIC AND RAFTER ASSEMBLIES.  (a) This
section applies only to residential construction.
(b)  Notwithstanding any requirement contained in an energy
code adopted under Section 388.003(a) or (b), or a local amendment
adopted under Section 388.003(d), pertaining to the insulation of
unvented attic or unvented enclosed rafter assemblies, a local
jurisdiction shall consider an unvented attic or unvented enclosed
rafter assembly to be in compliance with the requirements of the
portion of the energy code administered and enforced by that local
jurisdiction pertaining to the insulation of unvented attic or
unvented enclosed rafter assemblies if:
(1)  the attic or rafter assembly is insulated and air
sealed with air impermeable insulation to an R-value of at least:
(A)  20 if the attic or rafter assembly is located
(B)  26 if the attic or rafter assembly is located
(2)  the building in which the attic or rafter assembly
(A)  attains a blower door test result of less
(B)  has a mechanical ventilation system that does
not rely solely on a negative pressure strategy;
(C)  if insulation is installed below the roof
deck and the exposed portion of the roof rafters is not already
covered by air impermeable insulation to an R-value of at least 20
or 26, as applicable, has the exposed portion of the roof rafters
wrapped in insulation to an R-value of at least 3, except that the
rafters are not required to be covered by insulation if:
(i)  the rafters are directly covered by
drywall or finished ceiling; or
(ii)  continuous insulation is installed
(D)  contains inside the building's thermal
envelope the building's indoor heating, cooling, and ventilation
SECTION 2.  This Act takes effect September 1, 2025.

Bill History

filed

Bill filed: AN ACT relating to certain energy efficiency performance standards for